UM HYDROCORE 160

UM HYDROCORE 160

Quantity
-
+
Min: 1
126 760.56 USD
Accept payment in USDT
Delivery time from 7 days
General Specifications
Dimensions (WD) 40GP: 40'8'8'6' / 12192mm × 2438mm × 2591mm
Miner capacity 192 pcs × Antminer S21
160 pcs × Antminer S21 Immersion
Oil volume (approximate) 925 gallons (3,500 liters) (including submerged miners)
Water requirement to be specified additionally
Weight (without fluid) 33,070 lbs (15,000 kg)
Operating weight (with liquid and miners) 42,000 lbs (19,000 kg)
Inlet/outlet pipe sizes 6 inches (DN 150)
Air Conditioner Optional
Power Supply
Input voltage & frequency 415~480V, 3-phase, 60Hz
Max. power consumption 1100 kW
Max. IT load 1056 kW
Power usage efficiency (PUE) 1.041
Max. current 1550A
Circuit breaker MCCB 2000A ABB/NOARK UL Listed
Cable entry 3 conductors / 700 kcmil * 4 + PE 700 kcmil * 1
Smart PDU
Quantity 8
Circuit Breaker Brand ABB/Noark 25A@10KAc UL Listed
Interfaces 24 outlets (S21) / 20 outlets (S21 Immersion)
Remote control Yes
Pumping system
Brand Grundfos
Number of pumps 2 oil pumps / 1 water pump
Capacity of oil pumps 748.5 GPM (170 m³/h) ΔP = 38.4 psi (265 kPa)
Water pump capacity 792.5 GPM (180 m³/h) ΔP = 36.3 psi (250 kPa)
Heat exchanger (BPHE)
Brand SWEP
Quantity 2
Capacity of each 550 kW
Dry Cooler
Brand Guntner/Kelvion
Heat dissipation capacity 1100 kW
Dimensions 29.4' * 6.9' * 8.3'
Inlet and outlet temperature Inlet: 138°F (59.3°C) / Outlet: 129°F (54°C)
Network and control
Control system Siemens intelligent remote control
Environment
Temperature range -31°F122°F (from -35°C to 50°C)
Humidity 5%~95% RH
Degree of Protection C3 / IP55
Outdoor noise level (at a distance of 10 meters) 68 dB
Indoor noise level 80 dB

UM Hydrocore 160 container is an advanced immersion cooling solution designed to efficiently accommodate high density equipment. With its scalable design, this container supports up to 160 S21Imm units or 192 S21 units for optimal thermal management using immersion cooling technology.

Advantages:

  • Full integration of immersion baths.
  • Heat dissipation via heat exchangers or external cooling towers.
  • Reduced wear and tear on equipment through soft cooling.
  • Stable operation even in extremely hot climate.

Request
a consultation

Our specialist will answer your questions

Investment amount, USD
Do you need a hosting service?
Select equipment state

Your application has been
successfully accepted!

Our manager will contact you within 30 minutes.