TANK | |
External Dimensions (WD) | 255' x 51' x 61' (7738mm x 1550mm x 1850mm) including PDU |
Number of servers | 192 servers |
Input voltage & frequency | 380V-415V, 3-phase, 50/60 Hz |
Total power | ≤1.2 MW |
Oil consumption | 951 gallons (3600 litres) including servers and CDUs |
Weight (estimated) | 6614 lbs (3000 kg) |
Operating weight (estimated) | 22050 lbs (10000 kg) including servers and fluid |
Input Wire Diameter | 8' (3 conductors + 4/0 AWG + PE 0 AWG) |
Smart PDU | |
Quantity | 8 |
Circuit Breaker | NOARK 20A/3P@10KAc UL Listed |
Interface | 24 SA2-30 sockets |
Fuses | 24*250A / 65KAc |
Current leakage protection | Yes |
Remote Control | Yes |
CDU (Circulating Cooling Unit) | |
Input voltage & frequency | 380V-415V, 3-phase, 50/60Hz |
Max. power consumption | 62 kW |
Input wire diameter | 4 conductors * 1 AWG + ground 2 AWG |
External dimensions (WD) | 129' x 54' x 57' (3890mm x 1660mm x 1730mm) |
Weight (estimated) | 5952 lbs (2700kg) |
Inlet/outlet port sizes | DN200*2 |
Oil pump | |
Brand | Grundfos |
Quantity | 2*15kW (20 hp) |
Capacity | 651 gallons per minute (147 m³/h) |
BPHE (Brazed Plate Heat Exchanger) | |
Brand | SWEP / Quantity: 2 |
Inlet and outlet temperature | Oil side: 142°F (61°C), 129°F (54°C) Water side: 122°F (50°C), 131°F (55°C) |
Capacity | Oil side: 705 GPM (160 m³/h) / Water side: 423 GPM (96 m³/h) |
Water pump | |
Brand | Grundfos |
Quantity | 30 kW (40 hp) |
Capacity | 846 GPM (192 m³/h) |
Control cabinet | |
PLC | Siemens S7-1200 |
VFD | Optional |
UM Deepcore Platform is a customizable indoor immersion cooling solution specifically designed for miners.
Its modular design provides flexible scalability and efficient heat management, ensuring optimal protection and extended lifespan for high-density equipment. Designed with reliability and energy efficiency in mind, UM Deepcore Platform is the best cooling solution for large-scale mining companies.
Advantages:
- Full integration of immersion baths.
- Heat dissipation via heat exchangers or external cooling towers.
- Reduced wear and tear on equipment through soft cooling.
- Stable operation even in extremely hot climate.

Request
a consultation
Our specialist will answer your questions